Ground Floor Room Info
Click any room or space to see more info
![Ground Floor Room Info](https://i0.wp.com/seaverseaver.com/wp-content/uploads/2022/01/room-numbers-ground-floor-1-1.png?fit=7317%2C3986&ssl=1)
Elevator
Elevator electrical in Room 27B, Panel LP0B. Elevator disconnect in Room 27B or Room 20 on Sitch Panel LP0.
Room 20
Mechanical Room
Contains the following: Electrical Switch LP0; Electrical Panel LP0A (key=777); Electrical Panel LP-Solar Installation (key=777), Solar Inverters; Fire Alarm main panel (Module XX); Water Softener (2005 & 2016); Water Heater x2 (2005 & 2016); Thermific Boiler (2005); Z-Max Lighting Control Panel (2005 & 2016 Exterior, Parking Lot Lights); Cross Connection Device
Electrical Circuits:
- 1: Thermific Boiler
- 3+5+7: Circulating Pumps
- 9: Water Heaters
- 19: Building Exterior Lights
- 20: Fire Alarm Panel
- 32: Lights
- 33: Boiler Circulating pumps
- 36: Exterior Lights, Z-Max Lighting Control Panel
- 38: Exterior Emergency Lighting
- 39+41: Parking Lot Lights
- 40: Carrier Controls Panel
- 42: LP0A Panel Outlet, Boiler Pump Disconnect
Water
- Cold Shutoff: at Water Softener
HVAC
- N/A
Room 22
Girls Home Locker Room
Electrical Circuits (Panel LP0A, Room 20):
- 11: Outlets
- 32: Lights
Water
- Cold Shutoff: CW-2 in hallway, above tiles
- Hot Shutoff: HW-2 in hallway, above tiles
HVAC
- Hydronic Ceiling Panels
Room 24
Boys Home Locker Room
Electrical Circuits (Panel LP0A, Room 20):
- 15: Outlets
- 30: Lights
Water
- Cold Shutoff: CW-2 in hallway, above tiles
- Hot Shutoff: HW-2 in hallway, above tiles
HVAC
- Hydronic Ceiling Panels
Room 26
PE Classroom
Electrical Circuits (Panel LP0A, Room 20):
- 15, 17: Outlets
- 28: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-0-2
Room 28
Athletics Office
Electrical Circuits (Panel LP0A, Room 20):
- 23: Outlets
- 28: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-0-1
Room 30
PE Storage
Electrical Circuits (Panel LP0A, Room 20):
- 23: Outlets
- 28: Lights
Water
- N/A
HVAC
- N/A
Room 32
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 1: Outlets
- 9: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-003
Room 34
Office
Electrical Circuits (Panel PP1, Room 44B):
- 1,3: Outlets
- 9: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-004
Room 36
Orchestra
Electrical Circuits (Panel PP1, Room 44B):
- 5: Outlets
- 9: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-005
Room 38
Choir
Electrical Circuits (Panel PP1, Room 44B):
- 2,5: Outlets
- 9: Lights
Water
- CW: CW-11 (via Ceiling Access Panel outside Room 38)
- HW: HW-11 (via Ceiling Access Panel outside Room 38)
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-007
Room 40
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 4: Outlets
- 9: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-006
Room 42
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 4: Outlets
- 9: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-006
Room 44A
Custodial Closet
Also has PA System Equipment
Electrical Circuits (Panel PP1, Room 44B):
- 11: Outlets
- 11: Lights
Water
- CW: CW-17 (Above tile, Room 46)
- HW: HW-17 (Above tile, Room 46)
HVAC
- N/A
Room 44B
Storage
Also has IT Rack, Phone Equipment
Electrical Circuits (Panel PP1, Room 44B):
- 15, 17, 19, 23: IT Rack Outlets
- 11: Lights
- 13: Fire Alarm Panel
- 27+29: Outside Amphitheater Outlet
Water
- N/A
HVAC
- N/A
Room 46
Girls Bathroom
Electrical Circuits (Panel PP1, Room 44B):
- 4: Outlets
- 11: Lights
Water
- CW: CW-17 (Above tile, Room 46)
- HW: HW-17 (Above tile, Room 46)
HVAC
- N/A
Room 48
Boys Bathroom
Electrical Circuits (Panel PP1, Room 44B):
- 4: Outlets
- 11: Lights
Water
- CW: CW-18 (Above tile, Room 48)
- HW: HW-18 (Above tile, Room 48)
HVAC
- N/A
Room 50A
Recording Studio Entry & Control Room
Electrical Circuits (Panel PP1, Room 44B):
- 10: Outlets
- 11: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-008
Room 50B
Recording Green Room
Electrical Circuits (Panel PP1, Room 44B):
- 10: Outlets
- 11: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-008
Room 52
Band Room
Electrical Circuits (Panel PP1, Room 44B):
- 14: Outlets
- 11: Lights
Water
- CW: CW-14 (Above tile, Room 46)
- HW: HW-14 (Above tile, Room 46)
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-009
Room 54
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 12: Outlets
- 11: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-010
Room 56
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 12: Outlets
- 11: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-010
Room 58
Practice Room
Electrical Circuits (Panel PP1, Room 44B):
- 12: Outlets
- 11: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-010
Room 21
Storage
Electrical Circuits (Panel LP0A, Room 20):
- 12: Outlets
- 26: Lights
Water
- N/A
HVAC
- N/A
Room 23
IT Room
Contains: Switches, Servers, Phone Equipment, Routers, PA Equipement
Electrical Circuits (Panel LP0A, Room 20):
- 16: Outlets
- 26: Lights
Water
- N/A
HVAC
- Passive
Room 25
Girls Away Locker Room
Electrical Circuits (Panel LP0A, Room 20):
- 12: Outlets
- 26: Lights
Water
- CW: CW-7, hallway above tile
- HW: HW-7, hallway above tile
HVAC (Boiler in Room 20, RTU via Room 239B)
- Hydronic Radiant Panel
Room 27A
Boys Away Locker Room
Electrical Circuits (Panel LP0A, Room 20):
- 12: Outlets
- 26: Lights
Water
- CW: CW-7, hallway above tile
- HW: HW-7, hallway above tile
HVAC (Boiler in Room 20, RTU via Room 239B)
- Hydronic Radiant Panel
Room 27B
Elevator Mechanical Room
Electrical Circuits (Panel LP0A, Room 20):
- 26: Lights
- Panel LP0B: Elevator lights, etc.
Water
- N/A
HVAC
- N/A
Room 29
Custodial Closet
Electrical Circuits (Panel LP0A, Room 20):
- 23: Outlets
- 26: Lights
Water
- CW: CW-7, hallway above tile
- HW: HW-7, hallway above tile
HVAC
- N/A
Room 31
Bathroom
Electrical Circuits (Panel LP0A, Room 20):
- N/A
- 26: Lights
Water
- CW: CW-10, above tile near Gym Stairs door
- HW: HW-10, above tile near Gym Stairs door
HVAC (Boiler in Room 20, RTU via Room 239B)
- Hydronic Radiant Panel
Gym
Gym & Stage
Electrical Circuits (Panel LP0A, Room 20):
- 25, 27, 29, 31: Outlets
- 37: Gym Floor Blowers
Electrical Circuits (Panel LP0, Room 20)
- 50 Amp Stage Lighting
- 50 Amp Outlet, West Wall
Electrical Circuits (Panel LP2A, Room 239B)
- 22, 24, 26, 28, 30: Gym Lights
- 32: Gym Emergency Lights (also controlled via WEMO switch next to panel)
- 23: West Basketball Backboard
- 25: East Basketball Backboard
- 33: Scoreboard
- 37: Divider Curtain
- 26: Lights
Water
- CW: CW-9 (Drinking Fountain), HS Commons, above tile
HVAC
- RTU, via Room 239B
Athletics Hallway
Athletics Hallway
Electrical Circuits (Panel LP0A, Room 20):
- 11, 15, 17: Outlets
- 13: Drinking Fountain
- 22: Lights
Water
- CW: CW-2, hallway above tile
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-0-1
Prefunc/HS Commons
Prefunc/HS Commons
Electrical Circuits (Panel LP0A, Room 20):
- 6, 8, 10, 21, 23: Outlets
- 2: Vending Machine
- 4: Refrigerator
- 24: Lights
Water
- CW: CW-2, hallway above tile
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-0-1
Gym Stairs
Athletics Stairs
Electrical Circuits (Panel LP0A, Room 20):
- 8: Outlets
- 34: Lights
Water
- N/A
HVAC
- N/A
Music Wing Hallway
Music Wing Hallway
Electrical Circuits (Panel PP1, Room 44B):
- 3, 4, 12: Outlets
- 8: Drinking Fountain
- 11: Lights
Water
- CW: CW-16 (Above tile, Room 46)
HVAC
- N/A
East Stairwell
East Stairwell
Electrical Circuits (Panel PP3, Room 248):
- 10: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- Cabinet Heater
First Floor Room Info
Click on any room or space to get more info
![First Floor Room Info](https://i0.wp.com/seaverseaver.com/wp-content/uploads/2022/01/room-numbers-first-floor-page-001-scaled.jpg?fit=2560%2C1909&ssl=1)
Room 101A
Classroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 11: Outlets
- 12: Lights
Water
- CW: CW-20 (Above tile, hallway near 102)
- HW: HW-20 (Above tile, hallway near 102)
HVAC
- TCS Basys Thermostat
- Furnace: Room 101C (Electrical: Panel HA in hall near Room 102, Circuit 2)
- CU: 9W (Electrical: Panel HA in hall near Room 102, Circuit 6+8)
Room 101B
Greenhouse
Electrical Circuits (Panel A, Hallway near Room 102):
- 15: Outlets
- 15: Lights
Water
- CW: CW-21 (Above tile, in Room 101)
- HW: HW-21 (Above tile, in Room 101)
HVAC
- Radiant Hydronic from Boiler in Room 114
Room 101C
Room 101 Mechanical Room
Electrical Circuits (Panel HA, Hallway near Room 102):
- 4: Outlets
- 4: Lights
Water
- CW: CW-22 (Outside faucet)
HVAC
- N/A
Room 102
Classroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 7, 9: Outlets
- 10: Lights
Water
- CW: CW-19 (Above tile, hallway near 102)
- HW: HW-19 (Above tile, hallway near 102)
HVAC
- Trane Thermostat
- Unit Ventilator: Room 101C (Electrical: Panel HA in hall near Room 102, Circuit 13)
- CU: 6E (Electrical: Panel HA in hall near Room 102, Circuit 15+17)
Room 103
Classroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 17: Outlets
- 19: GFCI Outlet
- 14: S. Lights
- 16: N Lights
Water
- CW: CW-24 (Above tile, hallway near 105)
- HW: HW-24 (Above tile, hallway near 105)
HVAC
- Honeywell Thermostat
- Furnace: Room 105B (Electrical: Panel HA in hall near Room 102, Circuit 25+27)
- CU: 12W (Electrical: Panel HA in hall near Room 102, Circuit 29+31)
Room104
Science Prep Room
Electrical Circuits (Panel A, Hallway near Room 102):
- 7: Outlets
- 8: Lights
- 1: Refrigerator
- 3: Dishwasher
- 5: Microwave & Vent Fan
Water
- CW: CW-19 (Above tile, hallway near 102)
- HW: HW-19 (Above tile, hallway near 102)
HVAC
- N/A
Room 105A
LS Kiln Room
Electrical Circuits (Panel HA, Hallway near Room 102):
- 24: Kiln Exhaust Fan
- 26+28: Kiln
Water
- N/A
HVAC
- N/A
Room 105B
Custodial Closet/Furnace Room
Electrical Circuits (Panel A, Hallway near Room 102):
- 19: Outlets
- 16: Lights
Water
- CW: CW-26 (Above tile, hallway near 107)
- HW: HW-26 (Above tile, hallway near 107)
HVAC
- N/A
Room 106
LS Art
Electrical Circuits (Panel A, Hallway near Room 102):
- 20, 22: Lights
Electrical Circuits (Panel HA, Hallway near Room 102):
- 19: Outlet
- 21: GFCI Outlet
Water
- CW: CW-25 (Above tile, hallway near 108)
- HW: HW-25 (Above tile, hallway near 108)
HVAC
- TCS Basys Thermostat
- Furnace: Room 108A (Electrical: Panel HB in hall near Room 112, Circuit 14+16)
- CU: 4E (Electrical: Panel HB in hall near Room 112, Circuit 5+7)
Room 107
Boys Bathroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 21: GFCI, Sink & Toilet Transformer
- 18: Lights
Water
- CW: CW-28 (Above tile, in Room 107)
- HW: HW-28 (Above tile, in Room 107)
HVAC
- N/A
Rooom 108A
Office
Electrical Circuits (Panel A, Hallway near Room 102):
- 22: Outlets
- 22: Lights
Water
- N/A
HVAC
- No Thermostat
- Furnace: Room 108A (Electrical: Panel HB in hall near Room 112, Circuit 1+3)
- CU: 4E (Electrical: Panel HB in hall near Room 112, Circuit 5+7)
Room 108B
Mechanical Room
Electrical Circuits (Panel A, Hallway near Room 102):
- 22: Outlets
- 22: Lights
Water
- N/A
HVAC
- N/A
Room 109
Girls Bathroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 21: GFCI, Sink & Toilet Transformer
- 18: Lights
Water
- CW: CW-28 (Above tile, in Room 107)
- HW: HW-28 (Above tile, in Room 107)
HVAC
- N/A
Room 110
Classroom
Electrical Circuits (Panel A, Hallway near Room 102):
- 24: Lights
Electrical Circuits (Panel HA, Hallway near Room 102):
- 20: GFCI Outlet
- 22: Outlets
Water
- CW: CW-25 (Above tile, near Room 108)
- HW: HW-25 (Above tile, near Room 108)
HVAC
- TCS Basys Thermostat
- Furnace: Room 108B (Electrical: Panel HB in hall near Room 112, Circuit 1+3)
- CU: 5E (Electrical: Panel HA in hall near Room 112, Circuit 18+20)
Room 111A
Tool Storage
Electrical Circuits (Panel A, Hallway near Room 102):
- 24: Lights
Electrical Circuits (Panel F, Hallway near Room 206):
- 22: Outlet
- 22: Lights
Water
- N/A
HVAC
- N/A
Room 111B
Storage Closet
Electrical Circuits (Panel F, Hallway near Room 206):
- 22: Lights
- 22: Outlets
Water
- N/A
HVAC
- N/A
Room 111C
Records Storage
Electrical Circuits (Panel B, Hallway near Room 112):
- 1: Lights
- 3: Outlets
Water
- N/A
HVAC
- N/A
Room 112A
Classroom
Electrical Circuits (Panel B, Hallway near Room 112):
- 8: Lights
- 4,6: Outlets
Water
- CW: CW-29 (Above tile, near Room 110)
- HW: HW-29 (Above tile, near Room 110)
HVAC
- TCS Basys Thermostat
- Furnace: Room 112C (Electrical: Panel HB in hall near Room 112, Circuit 2)
- CU: 3E (Electrical: Panel HB in hall near Room 112, Circuit 10+12)
Room 112B
Storage Closet
Electrical Circuits (Panel B, Hallway near Room 112):
- 6: Lights
- 6: Outlets
Water
- N/A
HVAC
- N/A
Room 112C
Mechanical Room
Electrical Circuits (Panel B, Hallway near Room 112):
- 4: Lights
Water
- N/A
HVAC
- N/A
Room 113A
Facilities Storage
Electrical Circuits (Panel B, Hallway near Room 112):
- 1: Lights
- 3: Outlets
Electrical Circuits (Panel K, Room 223B):
- 3: Lights
- 3: Outlets
Water
- CW: CW-30 (Room 113A)
- HW: HW-30 (Room 113A)
HVAC
- N/A
Room 113B
Facilities Office/ Mechanical Room
This room contains the main electrical switch gear for the entire building
Electrical Circuits (Panel E, Room 113B):
- 2: Lights
- 2, 7, 8, 10, 13, 15: Outlets
- 11: Fire Alarm Panel in Room 113B
- 8: Security & Door Panels
Electrical Circuits (Panel S, Room 113B):
- 11: Outlets
- 4: Lighting Control Panel
- 2: Carrier Router
- 1, 4, 6: LS Building Exterior Lights
- 3, 5, 7, 9: LS Parking Lot Pole Outlets
- 18+20, 22+24: LS Parking Lot Lights & Road Sign
- N/A
HVAC
- N/A
Room 114
Mechanical Room
Electrical Circuits (Panel D, Room 114):
- 19: Lights
- 19: Outlets
Electrical Circuits (Panel HD, Room 114):
- 3: Water Heater, Water Softener & DHW Circulating Pump
- 4: PK Boiler
- 5: HVAC Controls Panel
- 7: Weil-McLain Boiler
- 9: Boiler & Circulating Pump Control
- 27: Circulating Pump #1
- 33: Circulating Pump #2
Water
- CW: CW-33 (Room 114)
- HW: A-6 (Room 114)
HVAC
- N/A
Room 115
Laminator/Storage
Electrical Circuits (Panel D, Room 114):
- 4: Lights
- 4, 20, 22: Outlets
Water
- N/A
HVAC
- N/A
Room 116A
PreK Classroom
Electrical Circuits (Panel D, Room 114):
- 7, 10, 11, 17: Lights
- 13, 14, 15, 16
Water
- CW: CW-33 (Room 114)
- HW: HW-33 (Room 114)
HVAC
- No control or visibility
- 2 PTACs in use (Electrical Circuits: Panel HD, Room 114; 24+26, 28+30)
- 2 PTACs not in use (Electrical Circuits: Panel HD, Room 114; 13+15, 20+22)
Room 116B
PreK Bathroom
Electrical Circuits (Panel D, Room 114):
- 18: Lights
- 18: Outlets
Water
- CW: CW-33 (Room 114)
- HW: HW-33 (Room 114)
HVAC
- N/A
Room 117
IT Office
Electrical Circuits (Panel D, Room 114):
- 4: Lights
- 4, 20, : Outlets
Water
- N/A
HVAC
- Indirect, from AHU in Room 119. No visibility, no control.
Room 118
LS Library/Tinkerspace
Electrical Circuits (Panel C, Hallway near Room 118):
- 11: Lights
- 8: Outlets
Electrical Circuits (Panel HC, Hallway near Room 118):
- 5,6: Outlets
Water
- N/A
HVAC
- Furnace: Room 120D (Electrical: Panel HC in hall near Room 118, Circuit 1)
- CU: 1E (Electrical: Panel HC in hall near Room 118, Circuit 21+23+25)
Room 119
Mechanical Room/Storage
Electrical Circuits (Panel D, Room 114):
- 6: Lights
- 6,8: Outlets
- 24: AHU Control Panel
Water
- N/A
HVAC
- N/A
Room 120A
Student Services
Electrical Circuits (Panel C, Hallway near Room 118):
- 11: Lights
Electrical Circuits (Panel HC, Hallway near Room 118):
- 3: Outlets
Water
- N/A
HVAC
- Furnace: Room 120D (Electrical: Panel HC in hall near Room 118, Circuit 1)
- CU: 1E (Electrical: Panel HC in hall near Room 118, Circuit 21+23+25)
- Electric Radiant Panel: Panel HC in hall near Room 118, Circuit 31+33
Room 120B
Student Services
Electrical Circuits (Panel C, Hallway near Room 118):
- 11: Lights
Electrical Circuits (Panel HC, Hallway near Room 118):
- 5: Outlets
Water
- N/A
HVAC
- Furnace: Room 120D (Electrical: Panel HC in hall near Room 118, Circuit 1)
- CU: 1E (Electrical: Panel HC in hall near Room 118, Circuit 21+23+25)
Room 120C
Student Services
Electrical Circuits (Panel C, Hallway near Room 118):
- 11: Lights
Electrical Circuits (Panel HC, Hallway near Room 118):
- 5: Outlets
Water
- N/A
HVAC
- Furnace: Room 120D (Electrical: Panel HC in hall near Room 118, Circuit 1)
- CU: 1E (Electrical: Panel HC in hall near Room 118, Circuit 21+23+25)
- Electric Radiant Panel: Panel HC in hall near Room 118, Circuit 31+33
Room 120D
Mechanical Room
Electrical Circuits (Panel C, Hallway near Room 118):
- 11: Lights
- 9: Furnace Control Panel
Electrical Circuits (Panel HC, Hallway near Room 118):
- 3: Outlets
Water
- N/A
HVAC
- N/A
Room 121
Women's Bathroom
Electrical Circuits (Panel C, Hallway near Room 118):
- 18: Lights
- 18: Outlets
Water
- CW: CW-37 (Above tile, hall near Room 125)
- HW: HW-37 (Above tile, hall near Room 125)
HVAC
- N/A
Room 123
Men's Bathroom
Electrical Circuits (Panel C, Hallway near Room 118):
- 18: Lights
- 18: Outlets
Water
- CW: CW-37 (Above tile, hall near Room 125)
- HW: HW-37 (Above tile, hall near Room 125)
HVAC
- N/A
Room 124
Science Classroom
Electrical Circuits (Panel LP1A, Room 139):
- 1,3,5,13,15,17,19,21: Outlets
- 28: Lights
- 7: W Fume Hood
- 9: E Fume Hood
- 11: Dishwasher
Electrical Circuits (Panel LP0A, Room 20):
- 35: Front Desk Outlets
Water
- CW: CW-1 (Inside Room 20, above water softener)
- CW: CW-3 Front Sink (inside Room 22, above tile over lockers)
- CW: CW-48 Emergency Shower Trap Filler (above tile, Room 124)
- CW: CW-49 E. Range Hood Faucet (above tile, near E. sink Room 124)
- CW:CW-50 W. Range Hood Faucet (above tile, near W. sink Room 124)
- HW: HW-2 (Above tile, hall near Room 22)
- HW: HW-3 Front Sink
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-104
Room 125
Bistro
Electrical Circuits (Panel C, Hallway near Room 127):
- 13, 19: Outlets
- 19: GFCI Outlet
- 1: Refrigerator
- 17: Microwave
- 19: Refrigerator
- 20: GFCI Outlet
- 22: GFCI Outlet
- 24: Disposal & Dishwasher
- 16: Lights
Water
- CW: CW-37 (Above tile, hallway near Room 123)
- HW: HW-37 (Above tile, hallway near Room 123)
HVAC
- TCS Basys Thermostat
- Furnace: Room 127 (Electrical: Panel HC in hall near Room 118, Circuit 7+9)
- CU: 14W (Electrical: Panel HC in hall near Room 118, Circuit 8+10)
Room 126
Science Prep/Storage Room
Electrical Circuits (Panel LP1A, Room 139):
- 35: Outlets
- 30: Lights
- 37: Dishwasher
- 24: Fume Hood
- 26: Refrigerator
- 7: W Fume Hood
- 9: E Fume Hood
- 11: Dishwasher
Water
- CW: CW-4 (above tile, hall near Room 24)
- HW: HW-2 (Above tile, hall near Room 22)
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-105
Room 127
Custodial Closet
Electrical Circuits (Panel C, Hallway near Room 127):
- 17, 19: Outlets
- 16: Lights
Water
- CW: CW-40 (Above tile, hallway near Room 127)
- HW: HW-40 (Above tile, hallway near Room 127)
HVAC
- N/A
Room 128
Science Room
Electrical Circuits (Panel LP1A, Room 139):
- 25, 35: Outlets
- 30: Lights
- 24: Fume Hood
Water
- CW: CW-4 (above tile, hall near Room 24)
- CW: CW-6 (above tile, hall near Room 26)
- HW: HW-2 (Above tile, hall near Room 22)
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-106
Room 129A
Men's Bathroom
Electrical Circuits (Panel C, Hallway near Room 127):
- 15: Outlets & Flush Valve Transformer
- 14: Lights
Water
- CW: CW-43 Sink & Urinal (Above tile, hallway near Room 131)
- CW: CW-44 Toilet (Above tile, hallway near Room 131)
- HW: HW-43 (Above tile, hallway near Room 131)
HVAC
- TCS Basys Thermostat
- Furnace: Room 127 (Electrical: Panel HC in hall near Room 118, Circuit 15+17)
- CU: 15W (Electrical: Panel HC in hall near Room 118, Circuit 12+14)
Room 129B
Water Meter Closet
Electrical Circuits (Panel C, Hallway near Room 127):
- 14: Lights
Electrical Circuits (Panel P, Hallway near Room 133B):
- 25: Wellhouse GFCI/Heat Tape
- 37+39+41: Well Pump
Water
- N/A
HVAC
- N/A
Room 130
Classroom
Electrical Circuits (Panel LP1A, Room 139):
- 27,29: Outlets
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-107
Room 131
Women's Bathroom
Electrical Circuits (Panel C, Hallway near Room 127):
- 15: Outlets & Flush Valve Transformer
- 12: Lights
Water
- CW: CW-43 Sink & Small Toilet Stall (Above tile, hallway near Room 131)
- CW: CW-44 Large Toilet Stall (Above tile, hallway near Room 131)
- HW: HW-43 (Above tile, hallway near Room 131)
HVAC
- TCS Basys Thermostat
- Furnace: Room 127 (Electrical: Panel HC in hall near Room 118, Circuit 15+17)
- CU: 15W (Electrical: Panel HC in hall near Room 118, Circuit 12+14)
Room 132
Art Classroom
Electrical Circuits (Panel PP2, Room 136):
- 2,4: Outlets
- 16: Lights
Water
- CW: CW-11 (via Ceiling Access Panel, near Room 38)
- HW: HW-11 (via Ceiling Access Panel, near Room 38)
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-107
Room 133A
Hub/Cafeteria
Electrical Circuits (Panel P, Room 133B):
- 31,33: USB Outlets
- 16,18: E. Wall Outlets
- 8,10,12,14: Stage Outlets
- 11,13,15,17,19,21: Microwave Outlets
- 28: Milk Cooler Outlet
- 35: Outlet in Soffitt above single hallway door
- 29: Ceiling Projector Outlet
- 24: Ceiling Motorized Shade Outlets
- 26: Drinking Fountain
- 1: Can Lights
- 3,5,7,9: Ceiling Lights
- 4,6: Stage Lights
Water
- CW: CW-46 Drinking Fountain & Slop Sink (Room 133B)
- HW: HW-46Â Slop Sink ( Room 133D)
HVAC
- RTU & ERV Outside of Hub (Electrical Panel P, Room 133B, Circuits 38+40+42 & 30+32+34)
Room 133B
Mechanical Room
Electrical Circuits (Panel P, Room 133B):
- 23, 26, 35: Outlets
- 35: Lights
Water
- N/A
HVAC
- N/A
Room 133C
Events Storage
Electrical Circuits (Panel C, Hallway near Room 127):
- 12: Lights
Water
- N/A
HVAC
- N/A
Room 133D
Lunch Service Storage
Electrical Circuits (Panel C, Hallway near Room 127):
- 12: Lights
Water
- N/A
HVAC
- N/A
Room 133E
Lunch Service Storage
Electrical Circuits (Panel C, Hallway near Room 127):
- 13: Outlets
- 13: Lights
Water
- N/A
HVAC
- N/A
Room 134
Art Classroom
Electrical Circuits (Panel PP2, Room 136):
- 2,4: Outlets
- 16: Lights
Water
- CW: CW-11 (via Ceiling Access Panel, near Room 38)
- HW: HW-11 (via Ceiling Access Panel, near Room 38)
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-110
Room 135
Classroom
Electrical Circuits (Panel LP1A, Room 139):
- 2,4: Outlets
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-101
Room 136
Kiln Room
Electrical Circuits (Panel PP2, Room 136):
- 26,28: Outlets
- 1: PA Equipment Outlet
- 16: Lights
- 20+22: Kiln Outlet
Water
- N/A
HVAC
- N/A
Room 137
Classroom
Electrical Circuits (Panel LP1A, Room 139):
- 2,4: Outlets
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-101
Room 138
Girls Bathroom
Electrical Circuits (Panel PP2, Room 136):
- 6: Outlets
- 18: Lights
Water
- CW: CW-53 (above tile, Room 138)
- HW: HW-53 (above tile, Room 138)
HVAC
- N/A
Room 139
Office
Electrical Circuits (Panel LP1A, Room 139):
- 6: Outlets
- 38: Lights
Water
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-103
Room 140
Girls Bathroom
Electrical Circuits (Panel PP2, Room 136):
- 6: Outlets
- 18: Lights
Water
- CW: CW-53 (above tile, Room 138)
- HW: HW-53 (above tile, Room 138)
HVAC
- N/A
Room 141
Bathroom
Electrical Circuits (Panel LP1A, Room 139):
- 38: Lights
Water
- CW: CW-51 (above tile, Room 141)
- HW: HW-51 (above tile, Room 141)
HVAC (Boiler in Room 20, RTU via Room 239B)
- Hydronic Ceiling Panel
Room 142A
Makerspace
Electrical Circuits (Panel PP2, Room 136):
- 6,8,10: Outlets
- 8: Overhead Outlet Reels
- 16: Lights
Water
- CW: CW-54 (above tile, Room 140)
- HW: HW-54 (above tile, Room 140)
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-112
Room 142B
Art Classroom
Electrical Circuits (Panel PP2, Room 136):
- 11: Outlets
- 18: Lights
Water
- N/A
HVAC
- N/A
Room 143
Bathroom
Electrical Circuits (Panel LP1A, Room 139):
- 38: Lights
Water
- CW: CW-51 (above tile, Room 141)
- HW: HW-51 (above tile, Room 141)
HVAC (Boiler in Room 20, RTU via Room 239B)
- Hydronic Ceiling Panel
Room 144
Classroom
Electrical Circuits (Panel PP2, Room 136):
- 10,12: Outlets
- 18: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-113
Room 145
Office/Conference Room
Electrical Circuits (Panel LP1A, Room 139):
- 31: Outlets
- 32: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-108
Room 146
Art Classroom
Electrical Circuits (Panel PP2, Room 136):
- 12,13: Outlets
- 18: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-114
Room 147
Office
Electrical Circuits (Panel LP1A, Room 139):
- 31: Outlets
- 32: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-108
Room 149
Office
Electrical Circuits (Panel LP1A, Room 139):
- 31: Outlets
- 32: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-108
LS Science Stairs
LS Science Stairs
Electrical Circuits (Panel F, hall near Room 206):
- 24: Outlets
- 26: Lights (controlled via WEMO app)
Water
- N/A
HVAC
- N/A
LS Lower Hallway
LS Lower Hallway
Electrical Circuits (Panel A, hall near Room 102):
- 6: Outlets
- 4: Lights
Water
- N/A
HVAC
- N/A
LS Elevator Area
LS Lower Level Elevator Area
Electrical Circuits (Panel PP2, Room 136):
- 21: Drinking Fountain Outlet
- 4: Lights
Water
- N/A
HVAC
- N/A
Maintenance Entrance & Stairs
LS Maintenance Entrance & Stairs
Electrical Circuits (Panel F, hall near Room 206):
- 22: Lights (controlled via WEMO app)
Water
- N/A
HVAC
- N/A
LS Lower Level Cubbie Area
LS Lower Level Cubbie Area
Electrical Circuits (Panel B, hall near Room 112):
- 3: Outlets
- 1: Lights
Water
- N/A
HVAC
- N/A
PreK Hallway
PreK Hallway
Electrical Circuits (Panel D, Room 114):
- 8,12: Outlets
- 3: Drinking Fountain Outlet
- 1: Lights
Water
- CW: CW-35 (above tile, Room 116B)
HVAC
- N/A
Admin Playground Stairs
Admin Playground Stairs
Electrical Circuits (Panel D, Room 114):
- 5: Lights
Electrical Circuits (Panel J, behind LS Front Desk)
- 12: Outlets
Water
- N/A
HVAC
- N/A
K Playground Stairs
K Playground Stairs
Electrical Circuits (Panel D, Room 114):
- 5: Lights
Electrical Circuits (Panel J, behind LS Front Desk)
- 12: Outlets
Water
- N/A
HVAC
- N/A
Bistro Hallway
Bistro Hallway
Electrical Circuits (Panel C, hall near Room 127):
- 13: Outlets
- 10: Lights
Water
- CW: CW-46 (Room 133B)
- HW: HW-46 (Room 133D)
HVAC
- N/A
First Floor Connector Hallway
First Floor Connector
Electrical Circuits (Panel LP1A, Room 139):
- 41: Outlets & Cabinet Unit Heater
Electrical Circuits (Panel LP0A, Room 20):
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- Cabinet Unit Heater
Room 133F
Custodial Closet
Electrical Circuits (Panel C, Hallway near Room 127):
- 10: Lights
Water
- N/A
HVAC
- N/A
2005 Addition Hallway
2005 Addition Hallway
Electrical Circuits (Panel LP1A, Room 139):
- 21, 25: Outlets
- 36: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-103
MS/HS Lobby
MS/HS Lobby & Connector Hallway
Electrical Circuits (Panel LP1A, Room 139):
- 12: Outlets
- 8: Desk Outlets
- 20: Floor Outlets
- 39: Lobby Fireplace
- 29,31: Office Hallway Outlets
- 40: Lights
- 42: Lobby Display Case Lights
- 32: Office Hallway Lights
Water
- CW: CW-51 (above tile, Room 141)
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-103
Outside Storage Area
Outside Storage Area
Electrical Circuits (Panel LP1A, Room 139):
- 12: Outlets
- 38: Lights
- 22: Fire Alarm Panel
- 14+16: Wall Heater (Off)
Water
- N/A
HVAC
- Electric Wall Heater-off
Gym Stairs
Gym Stairwell
Electrical Circuits (Panel LP1A, Room 139):
- 12: Outlets
- 10: Cabinet Unit Heater
Electrical Circuits (Panel LP0A, Room 20):
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20)
- Cabinet Unit Heater
MS/HS Entrance Vestibule
HS Entry Vestibule
Electrical Circuits (Panel LP1A, Room 139):
- 10: Outlets, Door Access Control Panel (above tile) & Cabinet Unit Heater
- 36: Lights
Water
- N/A
HVAC (Boiler in Room 20)
- Cabinet Unit Heater
MS/HS Elevator
MS/HS Elevator
Electrical Circuits (Panel LP1A, Room 139):
- 18: Elevator Smoke Guard
Electrical Circuits (Panel LP0B, Room 127B):
- Car and Pit Lights, etc.
Elevator Disconnect via disconnect in Room 127B or LP0 Switch Gear in Room 20
Water
- N/A
HVAC
- N/A
2016 Atrium & Hallway
2016 Atrium & Hallway
Electrical Circuits (Panel PP2, Room 136):
- 2,5,6,10,13: Outlets
- 6: Hall Lights
- 7: Drinking Fountain
Electrical Circuits (Panel PP3, Room 248):
- 10: Atrium Ceiling Light
Water
- CW: CW-53 (above tile, Room 138)
HVAC (Boiler in Room 248, RTU access via Room 248)
- VAV-111 (Hallway)
- VAV-209 (Atrium)
LS Elevator
LS Elevator
Electrical Circuits (Panel HF, hall near Room 206):
- 12: Pit Light & Outlets
- 14: Elevator Car Lights
- 16: Elevator Pit Sump Pump
Elevator Disconnect:
- Panel HF, Circuits 18+20+22 (hall near Room 206)
- Disconnect Switch in Room 215
Water
- N/A
HVAC
- N/A
East Stairwell
2016 East Stairwell
Electrical Circuits (Panel PP3, Room 248):
- 10: Lights
Electrical Circuits (Panel PP1, Room 44B):
- 7: Cabinet Unit Heater
Water
- N/A
HVAC (Boiler in Room 248)
- Cabinet Unit Heater
Second Floor Room Info
Click on any room or space to get more info
![Second Floor Room Info](https://i0.wp.com/seaverseaver.com/wp-content/uploads/2022/01/room-numbers-second-floor-page-001-scaled.jpg?fit=2560%2C1887&ssl=1)
Room 200A
Classroom
Electrical Circuits (Panel F, Hallway near Room 206):
- 13,15: Outlets
- 18,20: Lights
Water
- CW: CW-20 (Above tile, hallway near 102)
- HW: HW-20 (Above tile, hallway near 102)
HVAC
- TCS Basys Thermostat
- Furnace: Room 202 (Electrical: Panel HF in hall near Room 206, Circuit 13)
- CU: 8W (Electrical: Panel HA in hall near Room 102, Circuit 1+3)
Room 200B
Office
Electrical Circuits (Panel F, Hallway near Room 206):
- 15: Outlets
- 15: Lights
Water
- N/A
HVAC
- N/A
Room 202
Mechanical Room
Electrical Circuits (Panel HF, Hallway near Room 206):
- 15: Outlets
- 15: Lights
- 13: Furnace for Room 200
- 11: Furnace for Room 204
Water
- N/A
HVAC
- N/A
Room 204
Classroom
Electrical Circuits (Panel F, Hallway near Room 206):
- 11,13,15: Outlets
- 14,16: Lights
Water
- CW: CW-20 (Above tile, hallway near 102)
- HW: HW-20 (Above tile, hallway near 102)
HVAC
- TCS Basys Thermostat
- Furnace: Room 202 (Electrical: Panel HF in hall near Room 206, Circuit 11)
- CU: 7W (Electrical: Panel HA in hall near Room 102, Circuit 5+7)
Room 206
Classroom
Electrical Circuits (Panel F, Hallway near Room 206):
- 9,11,17: Outlets
- 10,12: Lights
Water
- CW: CW-23 (Above tile, hallway near 103)
- HW: HW-23 (Above tile, hallway near 103)
HVAC
- TCS Basys Thermostat
- Furnace: Room 208 (Electrical: Panel HF in hall near Room 206, Circuit 7)
- CU: 10W (Electrical: Panel HB in hall near Room 112, Circuit 21+23)
Room 208
Mechanical Room
Electrical Circuits (Panel HF, Hallway near Room 206):
- 9: Outlets
- 9: Lights
- 7: Furnace for Room 206
- 5: Furnace for Room 210
Water
- N/A
HVAC
- N/A
Room 210
Classroom
Electrical Circuits (Panel F, Hallway near Room 206):
- 5,9: Outlets
- 6,8: Lights
Water
- CW: CW-23 (Above tile, hallway near 103)
- HW: HW-23 (Above tile, hallway near 103)
HVAC
- TCS Basys Thermostat
- Furnace: Room 208 (Electrical: Panel HF in hall near Room 206, Circuit 5)
- CU: 11W (Electrical: Panel HB in hall near Room 112, Circuit 25+27)
Room 212
Classroom
Electrical Circuits (Panel F, Hallway near Room 206):
- 1,3,5: Outlets
- 2,4: Lights
Water
- CW: CW-27 (Above tile, Room 107)
- HW: HW-27 (Above tile, Room 107)
HVAC
- TCS Basys Thermostat
- Furnace: Room 214 (Electrical: Panel HF in hall near Room 206, Circuit 1)
- CU: 13W (Electrical: Panel HB in hall near Room 112, Circuit 13+15)
Room 214
Mechanical Room
Electrical Circuits (Panel HF, Hallway near Room 206):
- 3: Outlets
- 3: Lights
- 1: Furnace for Room 212
Water
- N/A
HVAC
- N/A
Room 215
Elevator Mechanical Room
Electrical Circuits (Panel HF, Hallway near Room 206):
- 10: Outlets
- 10: Lights
- 18+20+22: Elevator Disconnect
Water
- N/A
HVAC
- N/A
Room 216
Room 217
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 4: Lights
- 2: Hand dryer-off
Water
- CW: CW-31 (above tile, hall near 112)
- HW: HW-31 (above tile, hall near 112)
HVAC
- N/A
Room 218A
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 14,19: Outlets
- 5: Lights
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 218B
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 23: Outlets
- 5: Lights
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 219
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 4: Light
- 6: Hand dryer-off
Water
- CW: CW-31 (above tile, near Room 112)
- HW: HW-31 (above tile, near Room 112)
HVAC
- N/A
Room 220A
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 11,13,23: Outlets
- 5: Lights
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 220B
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 11,15: Outlets
- 5: Lights
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 221
Copier Room
Electrical Circuits (Panel G, Hallway near Room 217):
- 20: Copier Outlets
- 22: Lights
- 24: Outlet for PA System Equipment
Water
- N/A
HVAC
- N/A
Room 222A
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 9,13: Outlets
- 5: Lights
- 5: PA System Outlet
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 222B
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 9,13,15: Outlets
- 5: Lights
Water
- N/A
HVAC
- Furnace: Room 220C (Electrical: Panel HG in hall near Room 217, Circuit 8)
- CU: 2E (Electrical: Panel HB in hall near Room 112, Circuit 29+31)
- Radiant Heat Panels: (Electrical: Panel HG in hall near Room 217, Circuit 9+11 OR 13+15)
Room 222C
Office
Electrical Circuits (Panel G, Hallway near Room 217):
- 7: Outlets
- 7: Lights
Electrical Circuits (Panel HG, Hallway near Room 217)
- 8: Furnace
- 10: Carrier iVu Router
Water
- N/A
HVAC
- N/A
Room 223B
Pod Storage
Electrical Circuits (Panel K, Room 223B):
- 1,6: Outlets
Electrical Circuits (Panel G, hall near Room 217)
- 22: Lights
Water
- CW: CW-30 (Room 113B)
- HW: HW-30 (Room 113B)
HVAC
- N/A
Room 223A
Pod
Electrical Circuits (Panel J, behind LS Front Desk):
- 6,13,23: Outlets
- 16: Floor Outlet-off
- 26,28,33: Lights
- 25: Emergency Lights
Water
- N/A
HVAC (Boiler in Room 114, AHU in Room 119, CU outside Door 27)
Room 224A
Office
Electrical Circuits (Panel J, behind LS Front Desk):
- 10: Outlets
- 7,10: Lights
Water
- N/A
HVAC (Boiler in Room 114, AHU in Room 119, CU outside Door 27)
Room 224B
Office
Electrical Circuits (Panel J, behind LS Front Desk):
- 10: Outlets
- 7,10: Lights
Water
- N/A
HVAC (Boiler in Room 114, AHU in Room 119, CU outside Door 27)
Room 225A
LS Music Room
Electrical Circuits (Panel J, behind LS Front Desk):
- 37,41: Outlets
- 30,32,34,36,38,42: Lights
- 37: Lg Soundproof Room
- 39: Floor Outlet & N Soundproof Room
- 41: S Soundproof Room & PA Outlet on its roof
Water
- N/A
HVAC (Boiler in Room 114, AHU in Room 119, CU outside Door 27)
Room 226
Classroom
Electrical Circuits (Panel H, Hallway near Room 228A):
- 1,3,5: Outlets
- 2,4: Lights
Water
- CW: CW-38 (Above tile, hallway near Room 118)
- HW: HW-38 (Above tile, hallway near Room 118)
HVAC
- Furnace: Room 228A (Electrical: Panel HF, Room 228B, Circuit 27)
- CU: 16W (Electrical: Panel HF, Room 228B, Circuit 30+32+34)
Room 227
Used Uniform Closet
Electrical Circuits (Panel H, Hallway near Room 228A):
- 23: Lights
Water
- N/A
HVAC
- N/A
Room 228A
Mechanical Room
Electrical Circuits (Panel H, Hallway near Room 228A):
- 15: Outlets
- 15: Lights
Water
- N/A
HVAC
- N/A
Room 228B
Mechanical Room
Electrical Circuits (Panel H, Hallway near Room 228A):
- 17: Outlets
- 17: Lights
Water
- N/A
HVAC
- N/A
Room 229
Lost & Found Closet
Electrical Circuits (Panel H, Hallway near Room 228A):
- 23: Lights
Water
- N/A
HVAC
- N/A
Room 230A
Classroom
Electrical Circuits (Panel H, Room 228B):
- 1: Outlets
- 19: Toilet Flush Valve Transformer
- 6: Lights
Water
- CW: CW-39 (Above tile, hallway near Room 127)
- CW: CW-40 Toilets (Above tile, hallway near Room 129)
- HW: HW-39 (Above tile, hallway near Room 127)
HVAC
- N/A
Room 230B
Girls BAthroom
Electrical Circuits (Panel H, Room 228B):
- 11: Outlets
- 19: Toilet Flush Valve Transformer
- 8: Lights
Water
- CW: CW-42 ( Above tile in toilet stall, Room 129)
- CW: CW-40 Toilets (Above tile, hallway near Room 129)
- HW: HW-42 (Above tile in toilet stall, Room 129)
HVAC
- N/A
Room 230C
K Office
Electrical Circuits (Panel H, Room 228B):
- 21: Outlets
- 21: Lights
Water
- N/A
HVAC
- PTAC (Electrical Panel: HH, Room 228B, Circuits: 13+15)
Room 232
Classroom
Electrical Circuits (Panel H, Hallway near Room 228A):
- 7,9: Outlets
- 10,12: Lights
Water
- CW: CW-45 (Room 133D)
- HW: HW-45 (Room 133D)
HVAC
- Furnace: Room 228B (Electrical: Panel HF, Room 228B, Circuit 25)
- CU: 17W (Electrical: Panel HF, Room 228B, Circuit 24+26+28)
Room 234
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 3: Outlets
- 8: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-204
Room 236
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 5: Outlets
- 8: Lights
Water
- CW: CW-47 (above tile, hall near Room 124)
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-205
Room 237
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 4,6: Outlets
- 18: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-201
Room 238
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 9: Outlets
- 10: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-206
Room 239A
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 4: Outlets
- 2,16: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-202
Room 239B
Mechanical Room
Electrical Circuits (Panel LP2A, Room 239B):
- 16: Lights
- 27: Fire Alarm Panel
- 31: HVAC Transformer
Water
- N/A
HVAC
- N/A
Room 240
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 11: Outlets
- 10: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-207
Room 241
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 21: Outlets
- 16: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-203
Room 242
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 13,20: Outlets
- 12,14,: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-208
Room 243
Bathroom
Electrical Circuits (Panel LP2A, Room 239B):
- 16: Lights
Water
- CW: CW-51 (above tile, Room 141)
- HW: HW-51 (above tile, Room 141)
HVAC
- N/A
Room 244
Classroom
Electrical Circuits (Panel PP3, Room 248):
- 1,3: Outlets
- 8: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-210
Room 245
Classroom
Electrical Circuits (Panel LP2A, Room 239B):
- 16: Lights
Water
- CW: CW-51 (above tile, Room 141)
- HW: HW-51 (above tile, Room 141)
HVAC
- N/A
Room 246
Classroom
Electrical Circuits (Panel PP3, Room 248):
- 3,5: Outlets
- 8: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-211
Room 247A
College Advising Center
Electrical Circuits (Panel LP2A, Room 239B):
- 20,36,38: Outlets
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-203
Room 247B
College Advising Office
Electrical Circuits (Panel LP2A, Room 239B):
- 19: Outlets
- 14: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-203
Room 248
Girls Bathroom
Electrical Circuits (Panel PP3, Room 248):
- 22: Outlets
- 22: Lights
- 12: Lochinvar Boiler
- 14: Boiler Pumps
- 16: HVAC Control Panel
- RTU GFCI
Water
- N/A
HVAC
- N/A
Room 250
Girls Bathroom
Electrical Circuits (Panel PP3, Room 248):
- 2: Outlets
- 6: Lights
Water
- CW: CW-53 Sinks (above tile, Room 138)
- CW: CW-55 Toilets (above tile, Room 252)
- HW: HW-54 (above tile, Room 140)
HVAC
- N/A
Room 252
Girls Bathroom
Electrical Circuits (Panel PP3, Room 248):
- 2: Outlets
- 6: Lights
Water
- CW: CW-53 Sinks (above tile, Room 138)
- CW: CW-55 Toilets (above tile, Room 252)
- HW: HW-54 (above tile, Room 140)
HVAC
- N/A
Room 254
Classroom
Electrical Circuits (Panel PP3, Room 248):
- 5,7: Outlets
- 6: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-213
Room 256
Classroom
Electrical Circuits (Panel PP3, Room 248):
- 7,9: Outlets
- 10: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-214
Room 258
Classroom
Electrical Circuits (Panel PP3, Room 248):
- 9,11: Outlets
- 10: Lights
Water
- N/A
HVAC (Boiler in Room 248, RTU via Room 248)
- VAV-215
LS Science Stairs
LS Science Stairs
Electrical Circuits (Panel F, hall near Room 206):
- 24: Outlets
- 26: Lights (controlled via WEMO app)
Water
- N/A
HVAC
- N/A
LS South Hallway
LS South Hallway
Electrical Circuits (Panel F, hall near Room 206):
- 1,5,11,13,15: Outlets
- 22,26: Lights
Electrical Circuits (Panel G, hall near Room 217)
- 7: Outlets
Water
- N/A
HVAC
- N/A
LS Elevator
LS Elevator
Electrical Circuits (Panel HF, hall near Room 206):
- 12: Pit Light & Outlets
- 14: Elevator Car Lights
- 16: Elevator Pit Sump Pump
Elevator Disconnect:
- Panel HF, Circuits 18+20+22 (hall near Room 206)
- Disconnect Switch in Room 215
Water
- N/A
HVAC
- N/A
Maintenance Entrance & Stairs
LS Maintenance Entrance & Stairs
Electrical Circuits (Panel F, hall near Room 206):
- 22: Lights (controlled via WEMO app)
Water
- N/A
HVAC
- N/A
Cubbie Area
LS Maintenance Entrance & Stairs
Electrical Circuits (Panel G, hall near Room 217):
- 22: Lights
- 22: Outlets
Water
- N/A
HVAC
- N/A
Admin Playground Stairs
Admin Playground Stairs
Electrical Circuits (Panel D, Room 114):
- 5: Lights
Electrical Circuits (Panel J, behind LS Front Desk)
- 12: Outlets
Water
- N/A
HVAC
- N/A
LS Lobby & Entrance
LS Lobby
Electrical Circuits (Panel J, behind LS Front Desk):
- 7,8,12: Outlets
- 21: Drinking Fountain Outlets
- 31: Security System Outlet, soffit area
- 1,3,5,7,11,15,17,18: Lights
Electrical Circuits (Panel HJ, behind LS Front Desk):
- 3,5,7: Lights
Water
- CW:CW-34 223 Drinking Fountain (above tile, hall near Room 115)
- CW:CW-36 225 Drinking Fountain (above tile, hall near Room 119)
HVAC (Boiler in Room 114, AHU in Room 119, CU outside Door 27)
K Playground Stairs
K Playground Stairs
Electrical Circuits (Panel D, Room 114):
- 5: Lights
Electrical Circuits (Panel J, behind LS Front Desk)
- 12: Outlets
Water
- N/A
HVAC
- N/A
K Hallway
Kindergarten Hallway
Electrical Circuits (Panel H, Room 228B):
- 14: Lights
- 3,7: Outlets
- 13: Hallway Drinking Fountain
Water
- CW: CW-41 (above tile, Room 129)
HVAC
- N/A
Second Floor Connector Hallway
Second Floor Connector
Electrical Circuits (Panel LP1A, Room 139):
- 41: Outlets & Cabinet Unit Heater
Electrical Circuits (Panel LP0A, Room 20):
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20, RTU via Room 239B)
- Cabinet Unit Heater
2005 Second Floor Hallway
Second Floor Hallway
Electrical Circuits (Panel LP2A, Room 239B):
- 5,13,20,21: Outlets & Cabinet Unit Heater
- 20: Outlet above tile for PA System
- 7: Drinking Fountain Outlet
- 20: Lights
Water
- CW:CW-51 (above tile, Room 141)
HVAC (Boiler in Room 20, RTU via Room 239B)
- VAV-203
2016 Second Floor Hallway
2016 Atrium & Hallway
Electrical Circuits (Panel PP2, Room 136):
- 2,5,6,10,13: Outlets
- 6: Hall Lights
- 7: Drinking Fountain
Electrical Circuits (Panel PP3, Room 248):
- 1,10,11: Outlets
- 4: Drinking Fountain Outlet
- 10: Hallway Lights & Atrium Ceiling Light
Water
- CW: CW-55 (above tile, Room 252)
HVAC (Boiler in Room 248, RTU access via Room 248)
- VAV-111 (Hallway)
- VAV-209 (Atrium)
MS/HS Elevator
MS/HS Elevator
Electrical Circuits (Panel LP1A, Room 139):
- 18: Elevator Smoke Guard
Electrical Circuits (Panel LP0B, Room 127B):
- Car and Pit Lights, etc.
Elevator Disconnect via disconnect in Room 127B or LP0 Switch Gear in Room 20
Water
- N/A
HVAC
- N/A
Gym Stairs
Gym Stairwell
Electrical Circuits (Panel LP1A, Room 139):
- 12: Outlets
- 10: Cabinet Unit Heater
Electrical Circuits (Panel LP0A, Room 20):
- 34: Lights
Water
- N/A
HVAC (Boiler in Room 20)
- Cabinet Unit Heater
2016 East Stairwell
2016 East Stairwell
Electrical Circuits (Panel PP3, Room 248):
- 10: Lights
Electrical Circuits (Panel PP1, Room 44B):
- 7: Cabinet Unit Heater
Water
- N/A
HVAC (Boiler in Room 248)
- Cabinet Unit Heater
Room 225B
IT Room
Electrical Circuits (Panel J, behind LS Front Desk):
- 9,20,24: Outlets
- 20: Lights
Water
- N/A
HVAC
- N/A